Generator & Switchgear Technical Terms

A to Z Glossary Technical Terms

In this A to Z Glossary you will find further links to additional information as follows: -

library button image
Words: Words linked within web page text are explained in the A-Z: clicking on this word will take you directly to the definition of this term

finder
More information: If you click on further information you will either be linked within this site to relevant information or to other Burtonwood Group Websites that provide further information on the specific topic

download
Document: This will link you to the relevant document available to download on the Burtonwood Group or other External websites for selected relevant institutions

link
Website: The website link will connect you to other External websites of selected relevant institutions

Please note: Unless otherwise specified, neither Burtonwood Group nor any person acting on behalf of Burtonwood Group maintains or is responsible for the content of any of these sites. The listing of Burtonwood Group's name with any of these sites should not be misconstrued as an endorsement of the information in them unless this is explicitly stated.

A B C D E F G H I J K L M N O P Q R S T U V W X Y Z
A Go Back to Page Top  
Active Search Results (ASR) Active Search Results (ASR) is an independent Internet Search Engine using a proprietary page ranking technology with Millions of popular Web sites indexed. Handy website link
Alternating Current (AC) A type of current that alternates from positive to negative at regular intervals. AC is the standard type of current used in electrical distribution systems by utility power companies due to the ease that it travels through cabling. Electrical wall sockets in nearly all structures served with utility power provide AC power.  
Alternator An alternator is an electromechanical device that converts mechanical energy to electrical energy in the form of alternating current (AC).  
Amp The unit of measure for electrical current. See Ampere.  
Ampere Unit of electrical current. Handy website finder
Amperage Strength of electric current measured in amperes.  
Association of Manufacturers of Power Generating Systems (AMPS) The Association of Manufacturers of Power generating Systems (AMPS) is an independent association of 80 members and are leading designers, manufacturers, suppliers and installers of reciprocating diesel and gas engine electrical generating systems. Handy website link
Apparent Power The load power as expressed in VA or KVA. This value is usually greater than real power due to circuit reactance.  
Arc A luminous electric discharge (spark) resulting when current flows between two points that are not connected by an intentional conductor.  
B Go Back to Page Top  
Battery A group of cells connected in such a way that more current and/or voltage is delivered than from one cell. See Direct Current.  
Blackout An AC power failure lasting anywhere from a few cycles to several hours or even days in duration.  
Brownout Common term for under voltage, taken from the coloration of filament style light bulbs during under voltage conditions. See under voltage  
Burtonwood Burtonwood and Westbrook is a civil parish in the outermost suburbs of Warrington in Cheshire, England. Historically within Lancashire, the name Burtonwood is known worldwide as the location of the former RAF Burtonwood military base. Burtonwood village itself is a few miles away from the site of the former base. Handy website link
C Go Back to Page Top  
Capacitor A discreet electrical device that has two electrodes and an intervening insulator (a dielectric).
CAT5 Category 5 is a description of network cabling that consists of four twisted pairs of copper wire terminated by a RJ–45 connector.  
Cell A combination of two metal plates suspended in an electrolyte which, when connected to an external circuit, causes a current to flow.  
Charge Voltage The voltage that must be applied to storage batteries to maintain their maximum charge.  
Constructionline At the heart is a national online database, the UK's largest register for pre-qualified contractors and consultants to match project specifications in one easy transaction. Handy website link
Contractors Health & Safety Assessment Scheme (CHAS) The Contractors Health and Safety Assessment Scheme (CHAS) is dedicated to completing health and safety pre-qualification assessments to a nationally recognised and accepted threshold standard. Handy website link
Common Mode Voltage The voltage present when measuring between neutral to ground.  
Converter A device that changes DC to AC or a device that changes AC to DC.  
Current The flow of electricity in a circuit as expressed in amperes.  
Cycles per second This term describes the frequency of alternating current. Frequency is measured in "hertz" which is synonymous with cycles per second.  
D Go Back to Page Top  
Diesel Generator A diesel generator is the combination of a diesel engine with an electrical generator (often called an alternator) to generate electric energy. Diesel generating sets are used in places without connection to the power grid or as emergency power supply Handy website link
Dip A short duration brownout condition, usually in response to inductive loads starting and stopping. See brownout.  
Direct Current (DC) A type of electricity where current flows in one direction, without reversal such as from a battery.  
Distortion Any deviation from the normal sine wave for an AC quantity. Alternating waveforms with a square or rectangular wave shape can be said to carry some amount of distortion. Typically, a good AC supply waveform will carry 5% THD (total harmonic distortion) content or less. See harmonics, total harmonic distortion.  
Double Conversion UPS See online double conversion UPS.  
Dropout Voltage The voltage at which a device fails to operate properly and/or safely. Most computer systems will reboot, reset, or place save data at risk when line voltage falls below approximately 95–100VAC.  
E Go Back to Page Top  
Efficiency Ratio of output energy to input energy for a device. Often refers to the amount of energy lost in the form of heat during DC to AC inverter operation.
Electrical Interference [EMI, RFI] Acronyms for four types of electrical interference: Electromagnetic Interference, Radio Frequency Interference, Electromagnetic Pulse, and Electrostatic Discharge. All of which are unwanted signals common in noisy electrical environments.  
Energy Absorption The amount of electrical energy absorbed by a device measured in joules.  
Ethernet Ethernet is a widely used local-area network (LAN) protocol. Ethernet is a fast and reliable network solution.  
European Community Noise Directive 2000/14/EC Noise emission in the environment by equipment for use outdoors. European Parliament & EU Council Directive 2000/14/EC of 8 May 2000. Handy document download
External LAN adapter Expansion card used to connect a computer to a network.  
F Go Back to Page Top  
Feedback Energy that is fed from the output of a circuit back to its input.  
Filter An electronic device that blocks the passage of certain frequencies while allowing other frequencies to pass.  
Frequency The number of cycles (oscillation positive and negative) completed in one second. In North America, utility power completes 60 cycles per second or 60Hz.  
FTP Acronym for File Transfer Protocol. A standard way to transfer files between computers. The method has built–in error checking. FTP often refers to a standard way of transferring many types of files over the Internet.  
Fuse A device that automatically self-destructs when the current passing through exceeds the rated value of the fuse.  
G Go Back to Page Top  
Generator Combination of a motor driving an electrical generator. Diesel generator systems are frequently used in conjunction with electronic UPS systems for very long-term operation during extended power outages. In electricity generation, an electric generator is a device that converts mechanical energy to electrical energy. The reverse conversion of electrical energy into mechanical energy is done by a motor; motors and generators have many similarities. A generator forces electrons in the windings to flow through the external electrical circuit.. handy website finder
Ground A conducting connection, whether intentional or accidental, between an electrical circuit and the earth, or to some conducting body that serves in place of earth. See ground rod.  
Ground Loop The condition of having two or more ground references in a common system. When two or more grounds have a potential difference between them, current can flow. This flow of current is a new circuit or loop which can interfere with the normal operation of the system.  
Ground Rod A long metal rod driven 6–10 feet into the ground as dictated by local electrical codes near the electrical service entrance of a structure.  
H Go Back to Page Top  
Harmonic    
Harmonic Distortion Excessive harmonic content that distorts the normal sinusoidal wave form is harmonic distortion.  
Hertz (Hz) Refers to the frequency of alternating cycles in an AC waveform per second. In North America, utility power is provided at 60Hz. In Europe and most of the rest of the world, utility power is provided at 50Hz. See frequency deviation.  
High Voltage (HV) The International Electrotechnical Commission and its national counterparts (IET, IEEE, VDE, etc.) define high voltage circuits as those with more than 1000 V for alternating current and at least 1500 V for direct current, and distinguish it from low voltage (50–1000 V AC or 120–1500 V DC) and extra low voltage (<50 V AC or <120 V DC) circuits.  
Horsepower Horsepower (HP) is the name of several units of measurement of power. The most common definitions equal between 735.5 and 750 watts. Horsepower was originally defined to compare the output of steam engines with the power of draft horses. The unit was widely adopted to measure the output of piston engines, turbines, electric motors, and other machinery. The definition of the unit varied between geographical regions. Most countries now use the SI unit watt for measurement of power. With the implementation of the EU Directive 80/181/EEC on January 1, 2010, the use of horsepower in the EU is only permitted as a supplementary unit. Handy web page finder
Hot Swappable Battery Refers to the feature that allows the battery of a UPS to be changed (due to age or defect), without taking the unit (and its attached load) out of service.  
Hub Basic networking device that connects multiple computers together.  
I Go Back to Page Top  
Impedance Measured in ohms, impedance is the total opposition to current flow in a circuit where alternating current is flowing.  
Inductive Load Electrical load whose current wave form lags the voltage waveform thus having a lagging power factor. Some inductive loads such as electric motors have a large start-up current requirement. See Inrush Current.  
Inductor An electrical device consisting of a conductor that is coiled. Inductors can be used to block high-frequency transients. As deployed in surge suppression strips.  
Inrush Current The initial surge of a current into a load before it attains normal operating condition. Certain types of loads, such as motors, compressors, air conditioners, power tools and other large loads require 2–5 times the energy on start-up than they do continuously. Incandescent, filament style light bulbs tend to dim briefly when a motorized load, like a window air conditioner, pulls a high degree of inrush current on start-up.  
Inverter The subassembly of a UPS that converts DC power to AC power.  
IP Acronym for Internet Protocol. IP is an address of a computer or other network device on a network using IP or TCP/IP. For example, the number "166.70.10.23" is an example of such an address. These addresses are similar to an address used on a house and help data reach its appropriate location on a network.  
Isolation Transformer A transformer used to reduce or eliminate noise and create the equivalent of a dedicated or isolated ground circuit. These transformers are included in many larger UPS systems of 3kVA or larger. Standalone isolation transformers serve the function of removing common mode noise. See common mode voltage.  
J Go Back to Page Top  
Joule Measure of electrical energy, also refers to a surge suppressor's ability to absorb energy.  
K Go Back to Page Top  
KVA An acronym that stands for kilovolt amperes. This is a unit of measure of apparent power. (1 kVA = 1000VA) See VA. Handy web page finder
kW An acronym that stands for kilowatt (a unit of measure of real power). 1 kW = 1000 watts. See watt. Handy web page finder
L Go Back to Page Top  
LAN Acronym for Local-Area Network. A LAN is a network that has networking equipment and/or computers in close proximity to each other capable of communicating, sharing resources and information.  
Line Interactive UPS A UPS design based on a standby system with enhancements. Line interactive systems still switch to battery power when a redout occurs, but instead of also switching to battery power when brownouts or over voltages occur, a tap switching voltage regulation circuit activates to maintain usable power at the output continuously, without consuming battery power. The main benefit is that connected equipment can run straight through extended brownouts or over voltages without draining the battery. Line Interactive systems are widely considered mid-level products between basic standby UPS systems and higher end online UPS systems.  
Linear Load An electrical load device, which, in steady state operation, presents an essentially constant load impedance to the power source throughout the cycle of, applied voltage. Examples: space heaters and incandescent light bulbs. Linear loads included electronic devices that do not require heavy inrush currents. See inductive load, non-linear load.  
Load The electrical device that uses power supplied by the source.  
Load Banking A Load Bank is intended to accurately mimic the operational or ?real? load that a power source will see in actual application. The Load Bank develops an electrical load, applies the load to an electrical power source and converts or dissipates, the resultant power output of the source. Handy document download
Low Voltage (LV) The International Electrotechnical Commission defines low voltage as any voltage in the range 50–1000 V AC or 120–1500 V DC.  
M Go Back to Page Top  
MOV Acronym that stands for Metal Oxide Varistor. MOVs utilize the nonlinear resistance property of zinc oxide to form a variable resistor, whose resistance to current drops as voltage increases. Virtually all AC surge suppression strips employ MOV's as their main surge suppression component. See shunt.  
N Go Back to Page Top  
Neutral One if the conductors of a three phase wye system. The Neutral wire carries the entire current of a single–phase 120 volt circuit and the resultant current in a three-phase system that is unbalanced.  
Noise Unwanted electrical signals, which produce undesirable effects in the circuits of the control systems in which they occur. See electrical interference.  
Nominal Voltage A nominal value assigned to a circuit or system for the purpose of conveniently designating its voltage classes (120VAC, 208/240VAC, 12VDC, 24VDC, and 48VDC). For example, a 120V wall socket will rarely measure exactly 120 volts. The nominal (or named) voltage of 120V actually refers to a range of usable voltages centered around 120 volts. See CBEMA curve.  
Nonlinear Load Electrical load which draws current discontinuously or whose impedance varies throughout the cycle of the input ac voltage waveform. Electronic devices that pull a great deal of start-up current. Typically involves motors, heating elements or compressors. Examples: air conditioners, power tools, compressors, etc. See inductive load & non-linear load.  
Normal Mode Voltage A voltage that appears between or among active circuit conductors. A 120VAC wall receptacle should yield full nominal voltage between hot and neutral line connections. See common mode.  
O Go Back to Page Top  
Off Line UPS Another term for Standby UPS. See Standby UPS.  
OFTEC OFTEC is the Oil Firing Technical Association. OFTEC Certificate download
Online Double Conversion UPS A high end UPS design where output power is completely regenerated and passed to connected equipment with zero transfer time between line and battery power. Incoming AC power is converted to DC and then re-converted back to AC by a continuous duty inverter system. The dual conversion process completely regenerates the power flowing through an on line UPS, completely removing all surges, spikes, noise and other irregularities, providing pure, frequency regulated sine wave output at all times. Online, double conversion UPS systems are widely considered the best possible type of UPS available.  
Outage A long-term loss of voltage resulting from a localized utility failure.  
Over Voltage When used to describe a specific type of extended variation, over voltage refers to a voltage having a value of at least 10% above the nominal voltage for any lasting period of time. This occurrence may last a few seconds, or several hours to a continuous condition depending on the site and prevailing conditions. Over voltage differs from a surge because it's a condition of less severe voltage levels that lasts at minimum for several cycles.  
P Go Back to Page Top  
Peak Voltage A measurement of an AC waveform of the highest peak-to-peak voltage present on the waveform. A properly synthesized 120V nominal AC waveform will have a peak voltage (also known as "peak to peak" voltage) of approximately 170 volts.  
Phase A term used to describe the timing between two or more events tied to the same frequency.  
Plug-in Protectors Refers to power protection equipment with a plug and receptacles whereby users without knowledge of electrical wiring can install and properly protect equipment.  
Power Factor (True) The ratio of active power (watts) to apparent power (VA). Most computer related equipment has a power factor between .6 and .8. Power factor is the spread between VA and wattage. VA x power factor = watts. See formulas. Handy web page finder
Prime Power Prime power is the need for power, continuously and for long periods of time. It is often used in remote or developing areas of the world where there is no utility service, where available service is very expensive or unreliable, or where customers choose to self-generate their primary power supply. Handy website finder
Pseudo Sine Wave Describes an alternate AC waveform to sine wave and PWM sine wave. Considered a mid-level waveform by most, desirable for all but the most sensitive of critical of computing applications. Rather than the smooth arc typically associated with a sine waveform, a PWM sine wave offers several rectangular steps to help mimic the energy supply of a sine wave. During the 1990's most manufacturers of standby and line interactive UPS systems began providing products with PWM sine wave output. See PWM sine wave and sine wave.  
Q Go Back to Page Top  
R Go Back to Page Top  
Redundancy Duplicating devices to the extent that if one were to fail there would be an identical unit to replace the failed unit. Often employed in mission critical networking systems as "mirrored" or "redundant" servers where both machines are performing identical tasks. If one of these servers fails, the application will not cease functioning.  
Response Time The time it takes for a suppressor to sense a surge or spike and react to it.  
RJ-45 (Registered Jack-45) A telephone connector that holds up to eight wires. RJ-45 plugs and sockets are used in Ethernet and Token Ring Type 3 devices.  
Rolling Brownouts Rolling Brownouts - A condition where power utilities are forced to purposely create under voltages and redouts over their service area to free up capacity so that the entire system is not at risk for power failure. When power usage for a given area or community inch up above 95% of capacity, utilities may begin purposely creating brownouts. If the condition worsens and further brownouts will not free up enough energy, the next utility choice is to create redouts. See redout, undervoltage.  
S Go Back to Page Top  
safecontractor Assessment Scheme (SAFE) With more than 150 major clients and almost 18,000 contractor members, safecontractor is the fastest growing health and safety assessment scheme in the UK. Handy website link
Sag See under voltage.  
Shield As normally applied to instrumentation cables, the term refers to a conductive sheath (usually metallic) applied over the insulation of a conductor or conductors. This sheath provides the means to reduce coupling between the conductors so shielded and other conductors which may be susceptible to, or which may be generating unwanted electrostatic or electromagnetic fields (noise).  
Shunt AC and dataline surge suppressors re-direct, or shunt, surges present on AC and datalines out to safe electrical grounding systems. See suppressor.  
Sine Wave Describes an ideal waveform with a smooth arcing alternating waveform. All products using AC power are designed for use with sine wave output. Many high-end line interactive and online UPS products provide sine wave output at all times. See square wave and PWM sine wave.  
Single Phase Power Power protection products that are single phase, meaning they protect or pass power with a single AC waveform present. Long-range utility transmission power lines carry 3-phase power. See three-phase power.  
SNMP Acronym for Simple Network Management Protocol. A widely used network monitoring and control protocol. Data is passed from SNMP agents, which are hardware and/or software processes reporting activity in each network device (hub, router, bridge, etc.) to the workstation console used to oversee the network. The agents return information contained in a MIB (Management Information Base), which is a data structure that defines what is obtainable from the device and what can be controlled (turned off, on, etc.). Originating in the UNIX community, SNMP has become widely used on all major platforms.  
Spike Also called an Impulse is a disturbance of the voltage wave form that is less than about 1 millisecond. Voltages can rise to hundreds or even thousands of volts in a very short period of time.  
Square Wave Describes an alternate AC waveform to sine wave or PWM sine wave. Considered by many to be the least desirable waveform for critical computing applications. Rather than the smooth arc typically associated with a sine waveform, a square waveform is entirely rectangular and may provide a challenge the operation of certain sensitive pieces of electronics when used continuously or for long duration. Before 1990, many standby UPS systems available provided square wave output in battery mode. Certain lower end power inverters still offer square wave output. See PWM sine wave and sine wave.  
Standby UPS A UPS that passes line power straight through to the output when conditions are stable, but switches to battery power when line voltage drops near 100-105 volts. A basic UPS type typically used to protect home computers and computer workstations.  
Standby or Emergency Power An emergency power system is an independent power generation system that is legally required to feed equipment or systems whose failure may present a life safety hazard to persons or property. A standby power system refers to an independent power system that allows operation of a facility in the event of normal power failure. Handy website finder
Suppressor A power protection device able to recognize surge conditions and reacts by shunting excess energy away from equipment and out to the electrical grounding system.  
Surge A short term voltage increase that exceeds established upper limits for several cycles or more. Often confused with Spikes or Transients which last less than 1/2 cycle.  
Switch A network device that cross connects stations or LAN segments. Also known as a "frame switch," switches are available for Ethernet, Fast Ethernet, Token Ring and FDDI. ATM switches are generally considered in a category by themselves. Network switches are increasingly replacing shared media hubs in order to increase bandwidth. For example, a 16–port 100BaseT hub shares the total 100 Mbps bandwidth with all 16 attached nodes. By replacing the hub with a switch, each sender/receiver pair has the full 100 Mbps capacity. Each port on the switch can give full bandwidth to a single server or client station or it can be connected to a hub with several stations.  
Switching Power Supply The portion of a PC, Workstation, Server or other computing device that converts incoming AC power to the various DC voltages required by the internal components within the computer. Switching power supplies were incorporated into early PC designs due to their ability to withstand short duration losses in power of up to 100–200 milliseconds without rebooting computers. This is so because switching power supplies do not pull power continuously. Instead, they pull power in "gulps" several times per second.  
Switchgear The term switchgear when used in association with the electric power system, or grid, refers to the combination of electrical disconnects, fuses and/or circuit breakers used to isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. Handy website finder
T Go Back to Page Top  
TCP/IP Acronym for Transmission Control Protocol/Internet Protocol. TCP/IP was developed by the U.S. Department of Defense. TCP/IP is a language governing communications among all computers on the Internet. TCP/IP is two separate protocols, TCP and IP, which are used together. The Internet Protocol standard dictates how packets of information are sent out over networks. IP has a packet-addressing method that lets any computer on the Internet forward a packet to another computer that is a step (or more) closer to the packet's recipient. The transmission Control Protocol ensures the reliability of data transmission across Internet connected networks. TCP checks packets for errors and submits request for re-transmissions if errors are found; it also will return the multiple packets of a message into a proper, original sequence when the message reaches its destination.  
Three-Phase Power Electrical power supplied on three separate outputs with a phase difference of 120 degrees between any two of the outputs. Three-phase power is usually what's delivered to the service entrance of a building from the electrical utility. At the panel, the three phases are split into three single-phase legs. Large panel mount and multi-kVA UPS systems exist that function with three-phase power.  
Total Harmonic Distortion (THD) The ratio of the root-mean- square of the harmonic content to the root-mean-square value of the fundamental quantity, expressed as a percent of the fundamental. Typically a supply sine wave is considered acceptable when THD levels are 5% or less. See harmonics, harmonic distortion and distortion.  
Transfer Time The time it takes to switch from AC line power to battery power.  
Transformer A device used for changing the voltage of an AC circuit and/or isolation in a circuit from its power source.  
Transient Synonym for surge. See surge.  
U Go Back to Page Top  
Utilities Vendor Database (UDVB) Achilles provides supplier management services that are used by companies throughout the industry, including the power generation, transmission and distribution, nuclear, water, telecom and gas industries. Hndy website link
Under voltage When used to describe a specific type of long duration variation, refers to a measured voltage having a value at least 10% below the nominal voltage for a period of time greater than one minute. Under voltages frequently occur during air conditioning season due to peak power demands and may last only minutes or several hours, days or months in duration.  
UPS An acronym for Uninterruptible Power Supply. Any device that provides continuous, acceptable power to its dependent loads no matter what is (or is not) coming in on the commercial utility's power lines (within limits). See standby UPS, line interactive UPS & online double conversion UPS.  
User Replaceable Battery Refers to the feature that allows the battery of a UPS to be changed easily, without the need for disassembly of the unit.  
UTP Cable Short for Unshielded Twisted Pair cable, UTP cable is a popular type of cable used in computer networking that consists of two shielded wires twisted around each other.  
V Go Back to Page Top  
VA Abbreviation for Volt Amps. The unit of measurement of apparent power. Most UPS systems are rated in volt amps. Actual wattage is typically 60-70% of this figure. See formulas, watts, amps, and power factor.  
Volt A unit of measure for voltage. Voltage is electrical pressure that forces current to flow in a conductor, such as a wire. Handy website link
Voltage Regulator A circuit that has a constant output voltage when the input voltage fluctuates.  
Volt-ampere The unit of measurement of apparent power.  
W Go Back to Page Top  
Watt A unit of measure for true power consumption. Watts = VA divided by Power Factor. Handy website link
X Go Back to Page Top  
Y Go Back to Page Top  
Z Go Back to Page Top  

Secure Customer Login

Secure customer login

Call Us Now
+44 (0)1744 814444

Give us a call now

Email Us Now

Email us now for diesel generators

Latest News

Latest diesel generator & switchgear news

Latest Vacancies

Link to latest jobs

Follow Us On Google+

Link to BGSS Google+ page

Opening Hours

Details of Opening Hours

Adobe Software

If you require the latest version of Adobe® Reader®, click the icon below.

Adobe Reader

Web Site Search

Web search

If you can not find what you are looking for, use our web search facility